Specifications
| Range of product | Altivar Soft Starter ATS130 |
|---|---|
| Product or component type | Soft starter |
| Product destination | Asynchronous motors |
| Product specific application | Simple machine |
| Device short name | ATS130 |
| Network number of phases | 3 phases |
| Utilisation category | AC-53A |
| Ue power supply voltage | 200...480 V - 15...10 % |
| power supply frequency | 50...60 Hz +/- 5 Hz |
| [Ie] rated operational current | 45 A in line (at <40 °C) |
| Service factor at Ie | 100 |
| IP degree of protection | IP20 |
| Motor power kW | 11 kW at 230 V normal duty 22 kW at 400 V normal duty 22 kW at 440 V normal duty |
| Motor power hp | 10 hp at 200 V normal duty 10 hp at 208 V normal duty 15 hp at 230 V normal duty 30 hp at 460 V normal duty 30 hp at 480 V normal duty |
| Overload current profile | 300 % Ie for 5 s |
|---|---|
| On-load factor | 70 % |
| Operating cycles/hour | 35 cyc/h |
| Minimum motor current | 20 % Ie |
| Device connection | In line |
| [Us] control circuit voltage | 24 V DC +/- 10 % |
| Control power | 21.6 W starting and stopping 3 W steady state |
| Integrated motor overload protection | False |
| Protection type | Phase failure: mains Thermal protection: starter Bypass error: starter Control voltage Us: starter |
| Rated current pwr loss specification | 45 A |
| Power loss static current independent | 3 W |
| Power loss per device current dependent | 9 W |
| Power loss during starting | 264 W 300 % Ie |
| Standards | EN/IEC 60947-4-2 UL 60947-4-2 IEC 60664-1 |
| Product certifications | CE UKCA CCC RCM EAC UL |
| Marking | CE CCC UKCA RCM EAC |
| [Uc] control circuit voltage | 24 V DC |
| Discrete input number | 3 |
| Discrete input type | (DI) digital input, 10 kOhm (DI2) digital input, 10 kOhm (BOOST) digital input, 10 kOhm |
| Input compatibility | Discrete input level 1 PLC conforming to EN/IEC 61131-2 |
| Discrete input logic | Digital input at State 0: 0...< 5 V and <= 0.2 mA at State 1: > 13 V, >= 0.5 mA |
| Relay output number | 1 |
| Relay output type | Relay outputs R1A, R1C NO |
| Minimum switching current | 2.5 mA at 24 V DC for relay outputs |
| Maximum switching current | On resistive load for relay outputs : 1 A 250 V AC 400000 cycles On resistive load for relay outputs : 1 A 30 V DC 400000 cycles On inductive load for relay outputs : 1 A 250 V AC cos phi = 0.4 100000 cycles On inductive load for relay outputs : 1 A 30 V DC cos phi = 0.4 100000 cycles |
| Discrete output number | 1 |
| Discrete output type | Non programmable digital output DQ1 <= 30 V 200 mA |
| Display type | 1 LED (green) for control power energized 1 LED (yellow and red) for motor operation phases, errors |
| Display screen available | False |
| Operating position | Vertical +/- 30 degree |
| Height | 166 mm |
| Width | 55 mm |
| Depth | 165 mm |
| Product weight | 1.3 kg |
| Suitable for mounting onto standard rails | True |
| Function available | Deceleration voltage ramp Boost |
| internal bypass | True |
| material declaration | True |